ON:070213:en — FIRE CODE
Beta. Legal information, not legal advice. LEGALDIGM is not a law firm. Check the official source for the current text.
Analyze this law with AIFire Protection and Prevention Act, 1997
ONTARIO REGULATION 213/07
fire code
Consolidation Period:
From January 1, 2026 to the
e-Laws currency date
.
Last amendment:
303/25
.
Legislative History:
150/13
,
194/14
,
256/14
,
275/14
,
108/18
,
33/19
,
319/22
,
87/25
,
303/25
.
This is the English version of a bilingual regulation.
division a
compliance, objectives and functional statements
PART 1
compliance and General
SECTION 1.1 organization of this code
Subsection 1.1.1. General
Scope of Division A
1.1.1.1. Division A contains the compliance and application provisions,
objectives
and
functional statements
of this Code.
Scope of Division B
1.1.1.2. Division B contains the
acceptable solutions
of this Code.
Scope of Division C
1.1.1.3. Division C contains the administrative provisions of this Code.
Internal cross-references
1.1.1.4. If a provision of this Code contains a reference to another provision of this Code but no Division is specified, both provisions are in the same Division of this Code.
SECTION 1.2 COMPLIANCE
Subsection 1.2.1. Compliance with this Code
Owner’s responsibility
1.2.1.1. Unless otherwise specified, the
owner
is responsible for carrying out the provisions of this Code.
Compliance with Parts 2 and 3
1.2.1.2. Compliance with Parts 2 and 3 is required only as it relates to the use of
alternative solutions
as set out in Subsection 1.2.2.
Subsection 1.2.2. Compliance with Division B
1.2.2.1. (1) Compliance with Division B shall be achieved
(a) by complying with the
acceptable solutions
in Division B, or
(b) by using
alternative solutions
that
(i) will achieve the level of performance required by the applicable
acceptable solutions
in respect of the
objectives
and
functional statements
attributed to the applicable
acceptable solutions
in OFM Fire Code Supplement FCS-1, “Objectives and Functional Statements Attributed to Acceptable Solutions”,
(ii) do not contravene any other provision in Division B, and
(iii) have been
approved
and implemented in conformance with Subsection 1.3.2. of Division C.
(2) For the purpose of Clause (1)(b), the level of performance in respect of a
functional statement
refers to the performance required by the
functional statement
as it relates to the
objective
with which it is associated in OFM Fire Code Supplement FCS-1, “Objectives and Functional Statements Attributed to Acceptable Solutions”.
(3) The use of
alternative solutions
as described in Clause (1) (b) is not applicable in respect of any
acceptable solutions
to which
objectives
and
functional statements
have not been attributed in OFM Fire Code Supplement FCS-1, “Objectives and Functional Statements Attributed to Acceptable Solutions”.
Subsection 1.2.3. Compliance with Other Applicable Law
Compliance with other applicable law
1.2.3.1. Compliance with this Code does not relieve the
owner
from compliance with other applicable Acts and regulations, and, where a requirement of an applicable Act or regulation conflicts with a requirement of this Code, the more stringent requirement prevails, unless the more stringent requirement is in this Code and this Code says that the requirement of the other Act or regulation prevails.
SECTION 1.3 exemptions
Subsection 1.3.1. Exemption for Farms
Exemption
1.3.1.1. (1) Subject to Sentence (2) and Article 1.3.1.2., a
farm building
with an
occupant load
of not more than one person per 40 m
2
of
floor area
during normal use and other premises on a farm used for farming purposes are exempt from the requirements of this Code.
(2) Where a
floor area
or portion of a
floor area
within a
farm building
contains a
hazardous extraction
operation involving cannabis, the
floor area
or portion of the
floor area
shall comply with Articles 2.7.1.1. and 2.7.2.2., Section 2.8, Part 4, Article 5.1.4.2. and Subsection 5.14.11. of Division B.
Where compliance required
1.3.1.2. (1) A
farm building
shall comply with Part 2 and Part 6 of Division B if it is
(a) more than 600 m
2
in
building area
or more than 3
storeys
in
building height
, and
(b) constructed on or after January 1, 2025 to meet the requirements of the
Building Code
, as it read on or after that day, that apply to
farm buildings
.
SECTION 1.4 terms and abbreviations
Subsection 1.4.1. Definitions of Words and Phrases
Non-defined terms
1.4.1.1. (1) Definitions of words and phrases used in this Code that are not included in the list of definitions in Article 1.4.1.2. have the meanings that are commonly assigned to them in the context in which they are used, taking into account the specialized use of terms with the various trades and professions to which the terminology applies.
(2) Despite Sentence (1), words and phrases may be assigned other meanings where specifically noted in another provision of this Code.
Defined terms
1.4.1.2. The words and terms used in this Code that are in bold face, and either in upper and lower case or in lower case, have the following meanings:
Acceptable solution
means a requirement set out in Division B. (“
solution acceptable”)
Access to exit
means that part of a
means of egress
within a
floor area
that provides access to an
exit
serving the
floor area
. (“accès à l’issue”)
Agricultural occupancy
means the
occupancy
of a
building
or part thereof that is located on land that is associated with and devoted to the practice of farming and is used for the purpose of producing crops, raising farm animals or preparing, marketing, storing or processing agricultural products. (“établissement agricole
”)
Agricultural occupancy with no human occupants
means an
agricultural occupancy
that is not intended to be occupied by persons under normal use and is generally used for the storage of agricultural materials and by-products. (“établissement agricole sans occupation humaine”)
Air-supported structure
means a structure that consists of a pliable membrane that achieves and maintains its shape and support by internal air pressure. (“structure gonflable”)
Alarm signal
means an audible signal transmitted throughout a zone or zones or throughout a
building
to advise occupants that a fire emergency exists. (“signal d’alarme”)
Alert signal
means an audible signal to advise designated persons of a fire emergency. (“signal d’alerte”)
Alternative solution
means a substitute for an
acceptable solution
. (“solution de rechange”)
Appliance
means a device to convert fuel into energy, and includes all components, controls, wiring and piping required to be part of the device by the applicable standard referred to in this Code. (“appareil”)
Approved
means approved by the
Chief Fire Official
. (“approuvé”)
Architect
means a member or licensee of the Ontario Association of Architects under the
Architects Act
. (“architecte”)
Assembly occupancy
means the
occupancy
or the use of a
building
, or part thereof, by a gathering of persons for civic, political, travel, religious, social, educational, recreational or like purposes or for the consumption of food or drink. (“établissement de reunion”)
Atmospheric storage tank
means a
storage tank
that is designed to operate at pressures from atmospheric to 3.5 kPa (gauge). (“réservoir de stockage sous pression atmosphérique”)
Attic space
means the space between the roof and the ceiling of the top
storey
or between a dwarf wall and a sloping roof. (“comble”)
Basement
means a
storey
or
storeys
of a
building
located below the
first
storey
. (“sous-sol”)
Boiler
means an
appliance
intended to supply hot water or steam for
space heating
, processing or power purposes. (“chaudière”)
Breeching
means a
flue
pipe
or chamber for receiving
flue
gases from one or more
flue
connections and for discharging these gases through a single
flue
connection. (“collecteur de fumée”)
Building
means any structure used or intended for supporting or sheltering any use or
occupancy
. (“bâtiment”)
Building area
means the greatest horizontal area of a
building
above
grade
within the outside surface of exterior walls or within the outside surface of exterior walls and the centre line of
firewalls
. (“aire de bâtiment”)
Building Code
means any version of the
Ontario Building Code
that was in force at any time since it was made under
The Building Code Act, 1974
, the
Building Code Act
of the Revised Statutes of Ontario, 1980, the
Building Code Act
of the Revised Statutes of Ontario, 1990, the
Building Code Act, 1992
or a successor to the
Building Code Act, 1992
, and, where a specific version of the
Building Code
is referred to, that version of the
Building Code
. (“code du bâtiment”)
Building height
(in
storeys
) means the number of
storeys
contained between the roof and the floor of the
first storey
. (“hauteur de bâtiment”)
Business and personal services occupancy
means the
occupancy
or use of a
building
or part thereof for the transaction of business or the rendering or receiving of professional or personal services. (“établissement d’affaires”)
Care and treatment occupancy
means an
occupancy
in which persons receive special care and treatment. (“établissement de soins et de traitement”)
Care occupancy
means an
occupancy
in which special care is provided by a facility, directly through its staff or indirectly through another provider, to residents of the facility
(a) who require special care because of cognitive or physical limitations, and
(b) who, as a result of those limitations, would be incapable of evacuating the
occupancy
, if necessary, without the assistance of another person. (“
établissement de soins”)
Check
means visual observation to ensure the device or system is in place and is not obviously damaged or obstructed. (“verification”)
Chief Fire Official
means the assistant to the Fire Marshal who is the Municipal Fire Chief or a member or members of the
fire department
appointed by the Municipal Fire Chief under Article 1.1.1.2. of Division C or a person appointed by the Fire Marshal under Article 1.1.1.1. of Division C. (“chef de la sécurité-incendie”)
Chimney
means a primarily vertical shaft enclosing at least 1
flue
for conducting
flue
gases to the outdoors. (“cheminée”)
Class A fire
means a fire involving combustible materials such as wood, cloth and paper. (“feu de classe A”)
Class B fire
means a fire involving a
flammable
or
combustible liquid
, fat or grease. (“feu de classe B”)
Class C fire
means a fire involving energized electrical equipment. (“feu de classe C”)
Class D fire
means a fire involving a combustible metal. (“feu de classe D”)
Class K fire
means a fire involving combustible cooking media such as vegetable oils, animal oils and animal fats. (“feu de classe K”)
Closed container
means a container so sealed by means of a lid or other device that neither liquid nor vapour will escape from it at ordinary temperatures. (“récipient fermé”)
Closure
means a device or assembly for closing an opening through a
fire separation
, an exterior wall or an opening onto a fire escape that is required to be protected, which
(a) may include a door, a shutter, wired glass or glass block, and
(b) includes all components, such as hardware, closing devices, frames and anchors. (“
dispositif d’obturation”)
Combustible construction
means that type of construction that does not meet the requirements for
noncombustible
construction
or
encapsulated mass timber construction
. (“
construction combustible”)
Combustible dust
means dust and particles that are ignitable and liable to produce an explosion. (“
poussière combustible”)
Combustible fibres
means finely divided combustible vegetable or animal fibres and thin sheets or flakes of such materials that in a loose, unbaled condition present a flash fire hazard, and includes cotton, wool, hemp, sisal, jute, kapok, paper and cloth. (“fibres combustibles”)
Combustible liquid
means any liquid having a
flash point
at or above 37.8°C and below 93.3°C. (“liquide combustible”)
Compressed gas
means any contained mixture or material with either an absolute pressure exceeding 275.8 kPa at 21°C or an absolute pressure exceeding 717 kPa at 54°C, or both, or any liquid having an absolute
vapour pressure
exceeding 275.8 kPa at 37.8°C. (“gaz comprimé”)
Contained use area
means a supervised area containing one or more rooms in which occupant movement is restricted to a single room by security measures not under the control of the occupant. (“zone de détention cellulaire”)
Dangerous goods
means products, materials or substances that are
(a) regulated by the
Transportation of Dangerous Goods Regulations
, SOR/2001-286, made under the
Transportation of Dangerous Goods Act (Canada)
, or
(b) classified as hazardous products under the
Hazardous Products Regulations
, SOR/2015-17, made under the
Hazardous Products Act (Canada)
. (“marchandises dangereuses”)
Demolition
means the doing of anything in the removal of a
building
or any material part thereof. (“demolition”)
Detention occupancy
means an
occupancy
in which persons are under restraint or are incapable of self preservation because of security measures not under their control. (“établissement de detention”)
Dispenser sump
means a liquid-tight container intended for installation under a dispensing unit for the collection of any internal leakage of
flammable liquid
or
combustible liquid
from the dispensing unit. (“puisard de distributeur”)
Distilled beverage alcohol
means a beverage that is produced by fermentation and contains more than 20 per cent by volume of water-miscible alcohol. (“boisson alcoolique distillée”)
Distillery
means a
process plant
where
distilled beverage alcohols
are produced, concentrated or otherwise processed, and includes facilities on the same site where the concentrated products may be blended, mixed, stored or packaged. (“distillerie”)
Dwelling unit
means a
suite
operated as a housekeeping unit, used or intended to be used by one or more persons and usually containing cooking, eating, living, sleeping and sanitary facilities, and includes a
residential unit
. (“logement”)
Encapsulated mass timber construction
means that type of construction in which a degree of fire safety is attained by the use of encapsulated mass timber elements with an
encapsulation rating
and minimum dimensions for structural members and other
building
assemblies. (“construction en bois d’œuvre massif encapsule”)
Encapsulation rating
means the time in minutes that a material or assembly of materials will delay the ignition and combustion of encapsulated mass timber elements when it is exposed to fire under specified conditions of test and performance criteria. (“degré d’encapsulation”)
Exit
means that part of a
means of egress
, including doorways, that leads from the
floor area
it serves to a separate
building
, an open public thoroughfare or an exterior open space protected from fire exposure from the
building
and having access to an open public thoroughfare. (“issue”)
Facility
, for the purposes of Division A, means a property upon which a use regulated by this Code, including open air public assembly activities, open air industrial processing and outdoor storage, occurs, whether or not a
building
is located on the property. (“installation”)
Farm building
means a
building
or part thereof that contains an
agricultural occupancy
. (“
bâtiment agricole”)
Fire compartment
means an enclosed space in a
building
that is separated from all other parts of the
building
by enclosing construction that provides a
fire separation
having a required
fire-resistance rating
. (“compartiment résistant au feu”)
Fire damper
means a
closure
that consists of a damper installed in an air distribution system or in a wall or floor assembly that is normally held in the open position and that is designed to close automatically in the event of a fire in order to maintain the integrity of the
fire separation
. (“registre coupe-feu”)
Fire department
means a group of firefighters authorized to provide fire protection services by a municipality, group of municipalities or by an agreement made under section 3 of the
Fire Protection and Prevention Act, 1997
. (“service d’incendie”)
Fire detector
means a device which detects a fire condition and automatically initiates an electrical signal to actuate an
alert signal
or
alarm signal
and includes
heat detectors
and
smoke detectors
. (“détecteur d’incendie”)
Fire-protection rating
means the time in hours or fraction thereof that a
closure
, window assembly or glass block assembly will withstand the passage of flame when exposed to fire under specified conditions of
test
and performance criteria, or as otherwise prescribed in the
Building Code
. (“degré pare-flammes”)
Fire-resistance rating
means the time in hours or fraction thereof that a material or assembly of materials will withstand the passage of flame and the transmission of heat when exposed to fire under specified conditions of
test
and performance criteria, or as determined by extension or interpretation of information derived therefrom as prescribed in the
Building Code
. (“degré de résistance au feu”)
Fire separation
means a construction assembly that acts as a barrier against the spread of fire. (“
séparation coupe-feu”)
Fire stop
means a draft-tight barrier within or between construction assemblies that acts to retard the passage of smoke and flame. (“coupe-feu”)
Fire stop flap
means a device intended for use in horizontal assemblies that are required to have a
fire-resistance rating
and incorporate protective ceiling membranes and that operates to close off a duct opening through the membrane in the event of a fire. (“clapet coupe-feu”)
Firewall
means a
fire separation
of
noncombustible construction
that subdivides a
building
or separates adjoining
buildings
to resist the spread of fire that has a
fire-resistance rating
as prescribed in the
Building Code
and that has structural stability to remain intact under fire conditions for the required fire-rated time. (“mur coupe-feu”)
First storey
means the
storey
with its floor closest to
grade
and having its ceiling more than 1.8 m above
grade
. (“premier étage”)
Flame-spread rating
means an index or classification indicating the extent of spread of flame on the surface of a material or an assembly of materials as determined in a standard fire test as prescribed in the
Building Code
. (“
indice de propagation de la flamme”)
Flammable liquid
means a liquid having a
flash point
below 37.8ºC and having a
vapour pressure
not more than 275.8 kPa (absolute) at 37.8ºC as determined by ASTM D 323, “Vapor Pressure of Petroleum Products (Reid Method)”. (“liquide inflammable”)
Flash point
means the minimum temperature at which a liquid within a container gives off vapour in sufficient concentration to form an ignitable mixture with air near the surface of the liquid. (“point d’éclair”)
Floor area
means the space on any
storey
of a
building
between exterior walls and required
firewalls
, including the space occupied by interior walls and
partitions
, but not including
exits
,
vertical service spaces
and their enclosing assemblies. (“
aire de plancher”)
Flue
means an enclosed passageway for conveying exhaust gases. (“conduit de fumée”)
Flue collar
means the portion of a fuel-fired
appliance
designed for the attachment of the
flue pipe
or
breeching
. (“buse”)
Flue pipe
means the pipe connecting the
flue collar
of an
appliance
to a
chimney
. (“
tuyau de raccordement”)
Fuel-dispensing station
means any premises or part of premises at which
flammable liquids
or
combustible liquids
are dispensed from fixed equipment into the fuel tank of a motor vehicle, watercraft or floatplane. (“poste de distribution de carburant”)
Functional statement
means a function set out in Part 3. (“énoncé fonctionnel”)
Furnace
means a
space-heating appliance
that uses warm air as the heating medium and that usually has provision for the attachment of ducts. (“générateur d’air chaud”)
Grade
means the average level of finished ground adjoining a
building
at all exterior walls. (“niveau moyen du sol”)
Guest suite
means a single room or a series of rooms of complementary use providing sleeping accommodation for the travelling public or for recreational purposes in a
hotel establishment
. (“suite pour invites”)
Hazardous extraction
means a process to remove or separate a substance from a solution or mixture that involves the use of
flammable liquids
,
combustible liquids
or flammable gases as solvents in the process. (“extraction dangereuse”)
Heat detector
means a
fire detector
designed to operate at a predetermined temperature or rate of temperature rise. (“détecteur de chaleur”)
Heavy timber construction
means that type of
combustible construction
in which a degree of fire safety is attained by placing limitations on the sizes of wood structural members and on thickness and composition of wood floors and roofs, by avoidance of concealed spaces under floors and roofs and by use of
approved
fastenings, construction details and adhesives for structural members. (“construction en gros bois d’œuvre”)
High-hazard agricultural occupancy
means an
agricultural occupancy
containing sufficient quantities of highly combustible and flammable or explosive materials which, because of their inherent characteristics, constitute a special fire hazard. (“établissement agricole à risques très élevés”)
High-hazard industrial occupancy
means an
industrial occupancy
that contains sufficient quantities of highly combustible and flammable or explosive materials that, because of their inherent characteristics, constitute a special fire hazard. (“établissement industriel à risques très élevés”)
Hotel
means
floor areas
, a
floor area
or part of a
floor area
containing four or more
suites
that provide sleeping accommodation for the travelling public or for recreational purposes. (“hôtel”)
Hotel establishment
means a
building
containing a
hotel
and all subsidiary
occupancies
that are operated in connection with the
hotel
and includes all connected or adjacent
buildings
that are operated in connection with the
hotel
. (“établissement hotelier”)
Impeded egress zone
means a supervised area in which occupants have free movement but require the release, by security personnel, of security doors at the boundary before they are able to leave the area, but does not include a
contained use area
. (“zone à sortie contrôlée”)
Individual storage area
means the area occupied by piles, bin boxes,
racks
or shelves, including subsidiary aisles providing access to the stored products, which is separated from the adjacent storage by aisles. (“îlot de stockage”)
Industrial occupancy
means the
occupancy
or use of a
building
or part thereof for assembling, fabricating, manufacturing, processing, repairing or storing of goods and materials. (“établissement industriel”)
Inspection
means physical examination to determine that the device or system will apparently perform in accordance with its intended function. (“inspection”)
Interconnected floor space
means superimposed
floor areas
or parts of
floor areas
in which floor assemblies that are required to be
fire separations
are penetrated by openings that are not provided with
closures
. (“aire communicante”)
Listed
means equipment or materials included in a list published by a certification organization accredited by the Standards Council of Canada. (“répertorié”)
Low-hazard industrial occupancy
means an
industrial occupancy
in which the combustible content is not more than 50 kg/m
2
or 1200 MJ/m
2
of
floor area
. (“établissement industriel à risques faibles”)
Low pressure storage tank
means a
storage tank
designed to operate at pressures greater than 3.5 kPa (gauge) to 100 kPa (gauge). (“réservoir de stockage sous basse pression”)
Lower explosive limit
means the minimum concentration of vapour in air at which the propagation of flame occurs on contact with a source of ignition. (“limite inférieure d’explosivité”)
Major occupancy
means the principal
occupancy
for which a
building
or part thereof is used or intended to be used, and includes the subsidiary
occupancies
that are an integral part of the principal
occupancy
. (“usage principal”)
Marine fuel-dispensing station
means a
fuel-dispensing station
at which
flammable liquids
or
combustible liquids
are dispensed into the fuel tank of a watercraft or floatplane. (“poste marin de distribution de carburant”)
Means of egress
means a continuous path of travel provided for the escape of persons from any point in a
building
or contained open space to a separate
building
, an open public thoroughfare or an exterior open space protected from fire exposure from the
building
and having access to an open public thoroughfare.
Means of egress
includes both
exits
and
access to exits
. (“moyen d’évacuation”)
Medium-hazard industrial occupancy
means an
industrial occupancy
in which the combustible content is more than 50 kg/m
2
or 1200 MJ/m
2
of
floor area
and not classified as
high-hazard industrial occupancy
. (“établissement industriel à risques moyens”)
Mercantile occupancy
means the
occupancy
or use of a
building
or part thereof for the displaying or selling of retail goods, wares or merchandise. (“établissement commercial”)
Minimum explosible concentration
(MEC) means the minimum concentration of
combustible dust
suspended in air, measured in mass per unit volume, that will support a deflagration as defined by the test procedure in ASTM E 1515, “Standard Test Method for Minimum Explosible Concentration of Combustible Dusts”. (“concentration explosive minimale”)
Noncombustible construction
means that type of construction in which a degree of fire safety is attained by the use of noncombustible materials for structural members and other
building
assemblies. (“construction incombustible”)
Objective
means an objective set out in Part 2. (“
objectif”)
Occupancy
means the use or intended use of a
building
or part thereof for the shelter or support of persons, animals or property. (“usage”)
Occupant load
means the number of persons for which a
building
or part thereof is designed. (“nombre d’occupants”)
Order
means an order made under subsection 21(1) of the
Fire Protection and Prevention Act, 1997
. (“ordre”)
Owner
means any person, firm or corporation having control over any portion of the
building
or property under consideration and includes the persons in the
building
or property. (“propriétaire”)
Partition
means an interior wall, one
storey
or part of a
storey
in height, that is not load-bearing. (“cloison”)
Plenum
means a chamber forming part of an air duct system. (“plenum”)
Pressure vessel
means a
storage tank
that is designed to operate at pressures greater than 100 kPa (gauge). (“récipient sous pression”)
Process plant
means an
industrial occupancy
where materials, including
flammable liquids
,
combustible liquids
or Class 2 gases, are produced or used in a process. (“usine de transformation”)
Professional Engineer
means a person who holds a licence or a temporary licence under the
Professional Engineers Act
. (“
ingénieur”)
Public amusement area
means an area where the public is ordinarily invited or permitted access, either expressly or by implication, whether or not a fee is charged for entry, and includes entertainment displays or structures used on a temporary, seasonal or permanent basis. (“aire de divertissement public”)
Public corridor
means a corridor that provides
access to exit
from more than one
suite
. (“corridor commun”)
Rack
means any combination of vertical, horizontal or diagonal members that support stored materials on solid or open shelves, including both fixed and portable units. (“rayonnage”)
Rapid transit station
means a
building
or part thereof used for the purpose of loading and unloading passengers of a rapid transit system but does not include open-air shelters at street level. (“station de transport rapide”)
Refinery
means any
process plant
in which
flammable
or
combustible liquids
are produced from crude petroleum, including areas on the same site where the resulting products are blended, packaged or stored on a commercial scale. (“raffinerie”)
Refuse storage room
means a room in a
building
that is used for the storage of combustible refuse, including waste materials and recyclables. (“salle de stockage des déchets”)
Residential occupancy
means an
occupancy
in which sleeping accommodation is provided to residents who are not harboured for the purpose of receiving special care or treatment and are not involuntarily detained. (“habitation”)
Residential unit
means a
suite
operated as a housekeeping unit, used or intended to be used by one or more persons that contains cooking, eating, living, sleeping and sanitary facilities. (“unité d’habitation”)
Retirement home
means a retirement home regulated under the
Retirement Homes Act, 2010
. (“maison de retraite”)
Retrofit
means the minimum performance requirements for life safety for existing
buildings
. (“réaménagement”)
Self-service outlet
means a
fuel-dispensing station
, other than a marine
fuel-dispensing station
, where the public handles the dispenser. (“poste de distribution libre-service”)
Self-service storage building
means a
building
that is used to provide individual storage spaces to the public and that is open to the public only for those purposes. (“bâtiment de stockage libre-service”)
Service room
means a room in a
building
used to contain equipment associated with
building
services. (“local technique”)
Service space
means space in a
building
used to facilitate or conceal the installation of
building
service facilities such as chutes, ducts, pipes, shafts or wires. (“vide technique”)
Smoke alarm
means a combined
smoke detector
and audible alarm device that is designed to sound an alarm within the room or
suite
in which it is located when there is smoke within the room or
suite
. (“avertisseur de fumée”)
Smoke detector
means a
fire detector
designed to operate when the concentration of airborne combustion products exceeds a predetermined level. (“détecteur de fumée”)
Space heater
means a
space-heating appliance
that heats the room or space within which it is located without the use of ducts. (“poêle”)
Space-heating appliance
means an
appliance
that supplies heat to a room or space directly or indirectly or to rooms or spaces of a
building
through a heating system. (“générateur de chaleur”)
Spill containment sump
means a liquid-tight container intended to catch, retain and provide for the evacuation of any product at the time of filling. (“puisard de confinement des déversements”)
Spraying area
means the area that is within 6 m of a
spray booth
or spraying operation and that is not separated therefrom by a vapour-tight separation. (“aire de pulvérisation”)
Spray booth
means a power-ventilated structure that encloses or accommodates a spraying operation so that spray vapour and residue can be controlled and exhausted. (“cabine de pulvérisation”)
Spray room
means a
spraying area
on a
floor area
or part thereof in which an open spraying operation is confined and that is separated from the remainder of the
building
in which it is located by a noncombustible vapour-tight separation. (“atelier de pulvérisation”)
Sprinklered
(as applying to a
building
or part thereof) means that the
building
or part thereof is equipped with a system of automatic sprinklers. (“protégé par gicleurs”)
Storage garage
means a
building
or part of a
building
that is intended for the storage or parking of motor vehicles and that contains no provision for the repair or servicing of motor vehicles. (“
garage de stationnement”)
Storage tank
means a vessel for
flammable liquids
or
combustible liquids
having a capacity of more than 230 L and designed to be installed in a fixed location. (“
réservoir de stockage”)
Storey
means that portion of a
building
that is situated between the top of any floor and the top of the floor next above it, and where there is no floor above it, that portion between the top of the floor and the ceiling above it. (“étage”)
Street
means any highway, road, boulevard, square or other improved thoroughfare 9 m or more in width that has been dedicated or deeded for public use and is accessible to
fire department
vehicles and equipment. (“rue”)
Suite
means a single room or series of rooms of complementary use, operated under a single tenancy, and includes
dwelling units
, individual guest rooms in motels,
hotels
, boarding houses, rooming houses and dormitories, as well as individual stores and individual or complementary rooms for
business and personal services occupancies
. (“
suite
”)
Supervisory staff
means those occupants of a
building
who have some delegated responsibility for the fire safety of other occupants under the fire safety plan. (“
personnel de surveillance”)
Tank vehicle
means any vehicle, other than railroad tank cars and boats, with a cargo tank having a capacity of more than 450 L mounted or built as an integral part of the vehicle, used for the transportation of
flammable
or
combustible liquids
, and includes tank trucks, trailers and semi-trailers. (“véhicule-citerne”)
Tent
means a shelter or structure with a covering that is made of pliable material. (“tente”)
Test
means the operation of a device or system to ensure that it will perform in accordance with its intended operation or function. (“essai”)
Total area
means the total area of all floors above and below
grade
, including mezzanines and penthouses, measured between the inside surfaces of exterior walls or between the inside surfaces of exterior walls and the inside surfaces of
firewalls
. (“superficie totale”)
Transition sump
means an underground liquid-tight container intended for installation where mechanical connection or transition takes place for the collection of any internal leakage of
flammable liquid
or
combustible liquid
. (“puisard de transition”)
Travel distance
means the distance from any point in a
floor area
to an
exit
measured along the path of
exit
travel, except that when
floor areas
are subdivided into rooms used singly or into
suites
of rooms and served by
public corridors
or exterior passageways, the distance is measured from the door of the rooms or
suites
to the nearest
exit
. (“
distance à franchir”)
Turbine sump
means a container designed to provide access to equipment and to contain minor leakage, and installed to prevent water ingress.(“puisard de turbine”)
Unstable liquid
means a liquid, including a
flammable liquid
or
combustible liquid
, which is chemically reactive to the extent that it will vigorously react or decompose at or near normal temperature and pressure conditions or which is chemically unstable when subject to impact. (“
liquide instable”)
Vapour pressure
means the pressure exerted by a liquid as determined by ASTM D 323, “Standard Test Method for Vapor Pressure of Petroleum Products (Reid Method)”. (“
pression de vapeur”)
Vertical service space
means a shaft oriented essentially vertically that is provided in a
building
to facilitate the installation of
building
services, including mechanical, electrical and plumbing installations and facilities such as elevators, refuse chutes and linen chutes. (“
vide technique vertical”)
Viscosity
means the resistance that a liquid offers to flow. (“viscosité”)
Subsection 1.4.2. Symbols and Other Abbreviations
1.4.2.1. The symbols and abbreviations in this Code have the following meanings:
cm
centimetre(s)
cm/s
centimetre(s) per second
cm
2
square centimetre(s)
°C
degree(s) Celsius
h
hour(s)
kg
kilogram(s)
kN
kilonewton(s)
kPa
kilopascal(s)
L
litre(s)
L/h
litre(s) per hour
L/min
litre(s) per minute
L/min/m
2
litre(s) per minute per square metre
lx
lux
m
metre(s)
m
2
square metre(s)
m
3
cubic metre(s)
m/s
metre(s) per second
m/min
metre(s) per minute
m
3
/h
cubic metre(s) per hour
m
3
/min
cubic metre(s) per minute
min
minute(s)
MJ
megajoule(s)
mL
millilitre(s)
mm
millimetre(s)
mm
2
/s
square millimetre(s) per second
N
newton(s)
ppm
part(s) per million
s
second(s)
t
tonne(s)
%
per cent
SECTION 1.5 referenced documents
Subsection 1.5.1. Referenced Documents
Application of referenced documents
1.5.1.1. The provisions of documents referenced in this Code apply only to the extent that they are related to fire safety matters or to the risk created by the presence of unsafe levels of carbon monoxide.
Conflicting requirements
1.5.1.2. In the case of a conflict between the provisions of this Code and those of a referenced document, the provisions of this Code prevail.
Secondary references
1.5.1.3. If a document in this Code refers to another document, only those portions of the second document that are specific to the subject matter are applicable.
O. Reg. 213/07, Division A, Part 1; O. Reg. 150/13, s. 1; O. Reg. 194/14, ss. 1, 2; O. Reg. 256/14, ss. 1-3; O. Reg. 33/19, ss. 1-3; O. Reg. 87/25, ss. 1, 2, 95; O. Reg. 303/25, s. 1.
PART 2
objectives
SECTION 2.1 application
Subsection 2.1.1. Application
2.1.1.1. (1) The
objectives
set out in Table 2.2.1.1. apply only to the extent that they relate to an
alternative solution
as provided in Article 1.2.2.1.
(2) The
objectives
described in this Part apply only as they relate to fire safety or to the risk created by the presence of unsafe levels of carbon monoxide.
SECTION 2.2 objectives
Subsection 2.2.1. Objectives
2.2.1.1. The
objectives
of this Code are those listed in Table 2.2.1.1.
TABLE 2.2.1.1.
Objectives
Forming Part of Article 2.2.1.1.
Column 1
Category
Column 2
Objective number
Column 3
Objective
SAFETY
OS
An
objective
of this Code is to limit the probability that, as a result of specific circumstances related to the
building
or
facility
, a person in or adjacent to the
building
or
facility
will be exposed to an unacceptable risk of injury.
Fire Safety
OS1
An
objective
of this Code is to limit the probability that, as a result of
(a) activities related to the construction, use or
demolition
of the
building
or
facility
,
(b) the condition of specific elements of the
building
or
facility
,
(c) the design and construction of specific elements of the
facility
related to certain hazards, or
(d) inadequate built-in protection measures for the current or intended use of the
building
,
a person in or adjacent to the
building
or
facility
will be exposed to an unacceptable risk of injury due to fire.
The risks of injury due to fire addressed in this Code are those caused by:
OS1.1
fire or explosion occurring
OS1.2
fire or explosion impacting areas beyond its point of origin
OS1.3
collapse of physical elements due to a fire or explosion
OS1.4
fire safety systems failing to function as expected
OS1.5
persons being delayed in or impeded from moving to a safe place during a fire emergency
Safety in Use
OS3
An
objective
of this Code is to limit the probability that, as a result of
(a) activities related to the construction, use or
demolition
of the
building
or
facility
,
(b) of specific elements of the
building
or
facility
,
(c) the design and construction of specific elements of the
facility
related to certain hazards, or
(d) inadequate built-in protection measures for the current or intended use of the
building
,
a person in or adjacent to the
building
or
facility
will be exposed to an unacceptable risk of injury due to hazards.
The risks of injury due to hazards addressed in this Code are those caused by:
OS3.1
tripping, slipping, falling, contact, drowning or collision
OS3.2
contact with hot surfaces or substances
OS3.3
contact with energized equipment
OS3.4
exposure to hazardous substances
OS3.7
persons being delayed in or impeded from moving to a safe place during an emergency
HEALTH
OH
An
objective
of this Code is to limit the probability that, as a result of specific circumstances related to the
building
or
facility
, a person will be exposed to an unacceptable risk of illness.
Indoor Conditions
OH1
An
objective
of this Code is to limit the probability that, as a result of an installation required by this Code, a person in the
building
or
facility
will be exposed to an unacceptable risk of illness due to indoor conditions.
The risks of illness due to indoor conditions addressed in this Code are those caused by:
OH1.1
inadequate indoor air quality
Hazardous Substances Containment
OH5
An
objective
of this Code is to limit the probability that, as a result of
(a) activities related to the construction, use or
demolition
of the
building
or
facility
,
(b) the condition of specific elements of the
building
or
facility
,
(c) the design and construction of specific elements of the
facility
related to certain hazards, or
(d) inadequate built-in protection measures for the current or intended use of the
building
,
the public will be exposed to an unacceptable risk of illness due to the release of hazardous substances from the
building
or
facility
.
Fire Protection of
Buildings
and
Facilities
OP
An
objective
of this Code is to limit the probability that, as a result of specific circumstances related to the
building
or
facility
, the
building
or
facility
will be exposed to an unacceptable risk of damage due to fire.
Fire Protection of the
Building
or
Facility
OP1
An
objective
of this Code is to limit the probability that, as a result of
(a) activities related to the construction, use or
demolition
of the
building
or
facility
,
(b) the condition of specific elements of the
building
or
facility
,
(c) the design and construction of specific elements of the
facility
related to certain hazards, or
(d) inadequate built-in protection measures for the current or intended use of the
building
,
the
building
or
facility
will be exposed to an unacceptable risk of damage to due to fire.
The risks of damage due to fire addressed in this Code are those caused by:
OP1.1
fire or explosion occurring
OP1.2
fire or explosion impacting areas beyond its point of origin
OP1.3
collapse of physical elements due to a fire or explosion
OP1.4
fire safety systems failing to function as expected
Protection of Adjacent
Buildings
or
Facilities
from Fire
OP3
An
objective
of this Code is to limit the probability that, as a result of
(a) activities related to the construction, use or
demolition
of the
building
or
facility
,
(b) the condition of specific elements of the
building
or
facility
,
(c) the design and construction of specific elements of the
facility
related to certain hazards, or
(d) inadequate built-in protection measures for the current or intended use of the
building
,
adjacent
buildings
or
facilities
will be exposed to an unacceptable risk of damage to due to fire.
The risks of damage due to fire addressed in this Code are those caused by:
OP3.1
fire or explosion impacting areas beyond the
building
or
facility
of origin
O. Reg. 213/07, Division A, Part 2; O. Reg. 33/19, s. 4.
PART 3
functional statements
SECTION 3.1 application
Subsection 3.1.1. Application
3.1.1.1. The
functional statements
set out in Table 3.2.1.1. apply only to the extent that they relate to an
alternative solution
as provided in Article 1.2.2.1.
SECTION 3.2 functional statements
Subsection 3.2.1. Functional Statements
3.2.1.1. The
functional statements
of this Code are those set out in Table 3.2.1.1.
Table 3.2.1.1.
Functional Statements
Forming Part of Article 3.2.1.1.
Column 1
Function
Column 2
Functional Statement
F01
To minimize the risk of accidental ignition.
F02
To limit the severity and effects of a fire or explosion.
F03
To retard the effects of fire on areas beyond its point of origin.
F04
To retard failure or collapse due to the effects of fire.
F05
To retard the effects of fire on emergency egress
facilities
.
F06
To retard the effects of fire on
facilities
for notification, suppression and emergency response.
F10
To facilitate the timely movement of persons to a safe place in an emergency.
F11
To notify persons, in a timely manner, of the need to take action in an emergency.
F12
To facilitate emergency response.
F13
To notify emergency responders, in a timely manner, of the need to take action in an emergency.
F20
To support and withstand expected loads and forces.
F21
To limit or accommodate dimensional change.
F22
To limit movement under expected loads and forces.
F30
To minimize the risk of injury to persons as a result of tripping, slipping, falling, contact, drowning or collision.
F32
To minimize the risk of injury to persons as a result of contact with energized equipment.
F34
To resist or discourage unwanted access or entry.
F36
To minimize the risk that persons will be trapped in confined spaces.
F43
To minimize the risk of release of hazardous substances.
F44
To limit the spread of hazardous substances beyond their point of release.
F51
To maintain appropriate air and surface temperatures.
F80
To resist deterioration resulting from expected service conditions.
F81
To minimize the risk of malfunction, interference, damage, tampering, lack of use or misuse.
F82
To minimize the risk of inadequate performance due to improper maintenance or lack of maintenance.
O. Reg. 213/07, Division A, Part 3; O. Reg. 33/19, s. 5.
division b
acceptable solutions
PART 1
GENERAL
SECTION 1.1 General
Subsection 1.1.1. General
Notification
1.1.1.1. Where
tests
, repairs or alterations are made to fire protection installations, including sprinkler and standpipe systems, a procedure of notification shall be established, and the procedure shall include notifying the
fire department
and the
building
occupants where necessary for safety in the event of a fire emergency.
Check, inspect and test
1.1.1.2. (1) The
checking
,
inspection
and
testing
of fire safety devices shall be conducted in accordance with this Code.
(2) Where specific references to
checking
,
inspection
and
testing
of fire safety devices are not made in this Code, such devices shall be maintained to ensure they operate as per their design requirements.
(3) Any
appliance
, device or component of a device that does not operate or appear to operate as intended when
checked
,
inspected
or
tested
as required by this Code shall be repaired or replaced if the failure or malfunctioning of the
appliance
, device or component would adversely affect fire or life safety.
Subsection 1.1.2. Records of Tests and Inspections
Making of records
1.1.2.1. (1) If this Code requires
tests
and corrective measures or operational procedures to be carried out, records shall be made noting what was done and the date and time it was done.
(2) If this Code requires an
inspection
to be conducted in a supported group living residence or an intensive support residence regulated under the
Services and Supports to Promote the Social Inclusion of Persons with Developmental Disabilities Act, 2008
, a record shall be made noting what was
inspected
and the date and time of the
inspection
.
(3) The records described in Sentences (1) and (2) shall be retained at the
building
premises for examination by the
Chief Fire Official
.
(4) Electronic records that can be made readily available to the
Chief Fire Official
upon request, are deemed to comply with Sentence (3).
Retention of records
1.1.2.2. (1) Subject to Sentence (2), the original or a copy of any record required by this Code shall be retained at the
building
to which the record relates
(a) for a period of at least two years after being prepared, and
(b) so that at least the most recent and the immediately preceding record of a given
test
or
inspection
are retained.
(2) The initial verification or
test
reports for fire protection systems installed after November 21, 2007 shall be retained throughout the life of the systems, regardless of whether the systems are installed in accordance with this Code or the
Building Code
.
SECTION 1.2 referenced documents and organizations
Subsection 1.2.1. Referenced Documents
Applicable editions
1.2.1.1. (1) A reference in this Code to a document set out in Table 1.2.1.A. is to the edition designated in the table.
(2) Any
appliance
, equipment, system, installation or construction that met the requirements of this Article on December 31, 2025, as it read at the time, and that continues to meet those requirements is deemed to comply with the requirements of the edition referred to in Sentence (1).
Effective date
1.2.1.2. Unless otherwise specified in this Code, the documents referenced in this Code shall include all amendments, revisions and supplements effective to January 1, 2026.
Previous editions
1.2.1.3. Despite Articles 1.2.1.1. and 1.2.1.2., the
Chief Fire Official
may permit compliance with an edition of a document previous to that referred to in this Code if the
Chief Fire Official
is satisfied that compliance with the edition referred to in this Code is impractical.
TABLE 1.2.1.A.
Forming Part of Article 1.2.1.1.
Issuing Agency
Document Number
Title of Document
Code Reference
API
SPEC 5L (2012)
Line Pipe
4.5.2.1.(4)
API
SPEC 12B (2008)
Specification for Bolted Tanks for Storage of Production Liquids
4.3.1.2.(1)
API
SPEC 12D (2008)
Specification for Field Welded Tanks for Storage of Production Liquids
4.3.1.2.(1)
API
SPEC 12F (2008)
Specification for Shop Welded Tanks for Storage of Production Liquids
4.3.1.2.(1)
API
STD 620 (2013)
Design and Construction of Large, Welded, Low-Pressure Storage Tanks
4.3.1.3.(1)
API
STD 650 (2013)
Welded Tanks for Oil Storage
4.3.1.2.(1)
API
STD 653 (2009)
Tank Inspection, Repair, Alteration, and Reconstruction
4.3.1.10.(2)
Table 4.4.1.2.B.
API
STD 1104 (2013)
Welding of Pipelines and Related Facilities
4.5.5.2.(1)
4.5.10.7.(6)
API
STD 2000 (2009)
Venting Atmospheric and Low-Pressure Storage Tanks
4.3.1.2.(2)
4.3.4.1.(1)
API
RP 1604 (1996)
Closure of Underground Petroleum Storage Tanks
4.3.16.1.(1)
4.3.16.6.(1)
API
RP 2200 (2010)
Repairing Crude Oil, Liquefied Petroleum Gas and Product Pipelines
4.5.10.7.(6)
API
RP 2201 (2003)
Safe Hot Tapping Practices in the Petroleum and Petrochemical Industries
4.5.10.7.(6)
ASME
B16.5-2017
Pipe Flanges and Flanged Fittings NPS ½ Through NPS 24 Metric/Inch Standard
4.5.5.3.(1)
ASME
B31.3-2016
Process Piping
4.5.2.1.(5)
ASME
BPVC-2017
Boiler and Pressure Vessel Code
4.3.1.3.(1)
4.5.9.5.(2)
4.5.9.6.(1)
ASTM
A53/A53M-18
Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
4.5.2.1.(4)
ASTM
A193/A193M-17
Standard Specification for Alloy-Steel and Stainless Steel Bolting for High Temperature or High Pressure Service and Other Special Purpose Applications
4.5.5.4.
ASTM
D56-16a
Standard Test Method for Flash Point by Tag Closed Cup Tester
4.1.3.1.(1)
ASTM
D93-18
Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
4.1.3.1.(2)
ASTM
D323-15a
Standard Test Method for Vapor Pressure of Petroleum Products (Reid Method)
1.4.1.2. of Division A
(Vapour pressure)
ASTM
D3278-96
Standard Test Methods for Flash Point of Liquids by Small Scale Closed-Cup Apparatus
4.1.3.1.(4)
ASTM
D3828-16a
Standard Test Methods for Flash Point by Small Scale Closed Cup Tester
4.1.3.1.(3)
ASTM
E1515-14R22
Standard Test Method for Minimum Explosible Concentration of Combustible Dusts
1.4.1.2. of Division A
(Minimum explosible concentration)
CCBFC
NRCC-CONST-56437E 2020
National Fire Code of Canada 2020
7.3.1.2.
CCME
PN 1326 (2003)
Environmental Code of Practice for Aboveground and Underground Storage Tank Systems Containing Petroleum and Allied Petroleum Products
4.3.16.1.(1)
4.3.16.6.(1)
CFA
1990
Using the Canadian Fuels Colour-Symbol System to Mark Equipment and Vehicles For Product Identification
4.3.1.7.(1)
4.5.4.1.(3)
4.5.7.6.(1)
CGA
P-1 (2008)
Standard for Safe Handling of Compressed Gases in Containers
5.6.1.1.(3)
CGSB
CAN2-4.2-M77
Textile Test Methods
2.3.2.1.(2)
CSA
6.19-01
Residential Carbon Monoxide Alarming Devices
2.16.2.1.(6)
6.3.4.7.(4)
CSA
B51 : 19
Boiler, Pressure Vessel and Pressure Piping Code
4.3.1.3.(2)
CSA
B108-18
Natural gas refuelling stations installation code
4.6.1.1.(2)
CSA
B139 Series:19
Installation code for oil-burning equipment
4.3.13.6.
CSA
B149.1-15
Natural Gas and Propane Installation Code
4.6.1.1.(2)
CSA
B149.2-15
Propane Storage and Handling Code
4.6.1.1.(2)
CSA
B306-M1977
Portable Fuel Tanks for Marine Use
4.2.3.1.(1)
CSA
B346-M1980
Power-Operated Dispensing Devices for Flammable Liquids
4.6.3.1.
CSA
B365-17
Installation Code for Solid-Fuel-Burning Appliances and Equipment
2.6.2.1.
2.6.2.2.
CSA
B376-M1980
Portable Containers for Gasoline and Other Petroleum Fuels
4.2.3.1.(1)
CSA
B620-14
Highway Tanks and TC Portable Tanks for the Transportation of Dangerous Goods
4.2.3.1.(1)
CSA
C22.2 No. 141-15
Emergency Lighting Equipment
9.9.5.5.(2)
CSA
C22.2 No.152-1984 (R2011)
Combustible Gas Detection Instruments
5.17.3.3.(1)
CSA
C282-15
Emergency Electrical Power Supply for Buildings
6.7.1.1.(1)
6.7.1.3.
9.9.5.5.(1) and (2)
CSA
CAN/CSA- W117.2:19
Safety in Welding, Cutting and Allied Processes
5.17.1.2.
CSA
Z32-15
Electrical Safety and Essential Electrical Systems in Health Care Facilities
6.7.1.1.(2)
CSA
Z245.1-14
Steel Pipe
4.5.2.1.(4)
CSA
Z305.12-06 (R2021)
Safe Storage, Handling, and Use of Portable Oxygen Systems in Residential Buildings and Health Care Facilities
2.15.1.2.
IMO
2012
International Maritime Dangerous Goods Code
3.3.4.8.
MMAH
Supplementary Standard SB-4, January 1, 2024
Measures for Fire Safety in High Buildings
7.3.1.3.(2)
NACE
SP0285-2011-SG
Corrosion Control of Underground Storage Tank Systems by Cathodic Protection
4.3.10.1.(1)
NACE
SP0169-2013
Control of External Corrosion on Underground or Submerged Metallic Piping Systems
4.5.3.1.(1)
NFPA
10-2013
Standard for Portable Fire Extinguishers
6.2.7.1.(1) and (2)
NFPA
11-2016
Standard for Low-, Medium-, and High-Expansion Foam
2.1.3.5.(3)
4.3.2.5.(2)
NFPA
12-2015
Standard on Carbon Dioxide Extinguishing Systems
2.1.3.5.(3)
NFPA
12A-2015
Standard on Halon 1301 Fire Extinguishing Systems
2.1.3.5.(3)
NFPA
12B-1990
Standard on Halon 1211 Fire Extinguishing Systems
2.1.3.5.(3)
NFPA
13-2019
Standard for the Installation of Sprinkler Systems
3.2.1.8.(1)
3.2.1.9.
3.2.2.2.(5)
3.2.2.10.(3)
3.2.3.6.(1)
3.2.4.3.(4)
3.2.5.5.(1)
3.2.7.5.(3)
3.2.7.9.(1)
3.2.7.20.
4.2.8.4.(2)
4.9.4.3.(4)
5.4.2.3.
5.4.5.1.
5.12.8.2.(1)
5.13.6.1.
6.5.1.1.(1)
9.2.5.2.(4)
Table 9.2.5.A.
9.4.5.5.(2)
9.5.5.3.(2)
9.6.5.5.(2)
9.7.5.1.(1) and (4)
NFPA
13D-2016
Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes
6.5.1.1.(1)
9.7.5.1.(2)
9.8.5.1.
NFPA
13R-2019
Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height
6.5.1.1.(1)
9.4.5.5.(3)
9.5.5.3.(2)
9.7.5.1.(3)
NFPA
15-2017
Standard for Water Spray Fixed Systems for Fire Protection
2.1.3.5.(4)
4.3.2.5.(2)
NFPA
16-2019
Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems
2.1.3.5.(4)
NFPA
17-2017
Standard for Dry Chemical Extinguishing Systems
2.1.3.5.(3)
NFPA
17A-2017
Standard for Wet Chemical Extinguishing Systems
2.1.3.5.(3)
NFPA
18-2017
Standard on Wetting Agents
2.1.3.5.(5)
NFPA
20-2016
Standard for the Installation of Stationary Pumps for Fire Protection
9.4.5.5.(5)
9.7.5.1.(6)
NFPA
24-2013
Standard for the Installation of Private Fire Service Mains and their Appurtenances
4.9.4.3.(4)
NFPA
25-2017
Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
6.4.1.6.
6.5.1.1.(2)
6.6.1.5.(1) to (3)
NFPA
30-2018
Flammable and Combustible Liquids Code
4.2.7.6.(1)
4.3.16.1.(1)
4.3.16.6.(1)
NFPA
30B-2019
Code for the Manufacture and Storage of Aerosol Products
3.2.5.2.
3.2.5.5.(1)
NFPA
32-2016
Standard for Drycleaning Plants
5.14.10.1.(1)
NFPA
33-2018
Standard for Spray Application Using Flammable or Combustible Materials
5.12.1.1.(2)
5.12.3.5.
5.12.8.2.(2)
5.14.4.1.(2)
5.14.6.1.(3)
NFPA
37 2018
Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines
4.3.13.2.
NFPA
40-2022
Standard for the Storage and Handling of Cellulose Nitrate Motion Picture Film
5.4.4.2.
NFPA
40E-1993
Code for the Storage of Pyroxylin Plastic
5.4.3.3.(1)
NFPA
51-2018
Standard for Design and Installation of Oxygen-Fuel Gas Systems for Welding, Cutting and Allied Processes
5.17.2.1.
NFPA
55-2020
Compressed Gases and Cryogenic Fluids Code
5.6.1.1.(3) and (8)
NFPA
68-2013
Standard on Explosion Protection by Deflagration Venting
4.2.9.5.
4.3.14.3.
4.9.3.1.
4.9.4.2.(1)
5.3.1.6.(2)
5.6.2.4.(1)
5.18.3.3.(2) and (3)
NFPA
69 2014
Standard on Explosion Prevention Systems
4.3.2.5.(2)
4.9.4.2.(1)
5.3.1.7.(2)
NFPA
71-1989
Standard for the Installation, Maintenance and Use of Signaling Systems for Central Station Service
6.3.1.2.(2)
NFPA
72-2019
National Fire Alarm and Signaling Code
6.3.1.2.(5)
NFPA
82-2014
Standard on Incinerators and Waste and Linen Handling Systems and Equipment
2.6.3.1.(2)
2.6.3.2.
NFPA
86-2019
Standard for Ovens and Furnaces
4.5.8.5.(2)
5.18.4.1.
NFPA
91-2015
Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible Particulate Solids
4.1.7.2.(5)
5.1.4.2.(1)
5.5.4.3.(1)
NFPA
96-2014
Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations
2.6.1.12.(1)
2.6.1.13.
NFPA
291-2022
Recommended Practice for Fire Flow Testing and Marking of Hydrants
6.6.6.1.
NFPA
505-2018
Fire Safety Standard for Powered Industrial Trucks Including Type Designations, Areas of Use, Conversions, Maintenance, and Operation
3.4.1.1.
NFPA
664-2017
Standard for the Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities
5.3.2.1.(1)
NFPA
705-2018
Recommended Practice for a Field Flame Test for Textiles and Films
2.3.2.2.
2.9.2.1.
NFPA
1142-2022
Standard on Water Supplies for Suburban and Rural Fire Fighting
3.3.1.9.(4)
NFPA
2001-2022
Standard on Clean Agent Fire Extinguishing Systems
2.1.3.5.(3)
NRCan
Edition 3, 2014
Special Effects Pyrotechnics Manual
5.1.1.3.
NRCan
Second Edition, 2010
Display Fireworks Manual
5.1.1.3.
NRCC
User’s Guide - NBC 1995
Fire Protection, Occupant Safety and Accessibility (Part 3)
7.3.1.2.
OFM
Fire Code Supplement FCS-1, February 2025
Objectives and Functional Statements Attributed to the Acceptable Solutions
1.2.2.1.(1), (2) and (3) of Division A
1.3.2.2.(1) and (2) of Division C
STI/SPFA
SP031-2008
Standard for Repair of Shop Fabricated Aboveground Tanks for Storage of Flammable and Combustible Liquids
4.3.1.10.(2)
TC
2001
Standards Respecting Pipeline Crossings Under Railways
4.5.6.5.(3)
UL
ANSI/UL 558-1998
Industrial Trucks, Internal Combustion Engine‑Powered
3.4.2.1.(3)
UL
UL 2034-2008
Single and Multiple Station Carbon Monoxide Alarms
2.16.2.1.(6)
6.3.4.7.(4)
ULC
ANSI/CAN/UL/ULC 2258:2018
Standard for Aboveground Nonmetallic Tanks for Fuel Oil and Other Combustible Liquids
4.3.1.2.(1)
ULC
CAN/ULC-S109-14
Standard for Flame Tests of Flame-Resistant Fabrics and Films
2.3.2.1.(1)
ULC
ULC-S505-1974
Standard for Fusible Links for Fire Protection Service
9.5.3.7.(5)
ULC
CAN/ULC-S508-02
Standard for the Rating and Testing of Fire Extinguishers
6.2.2.1.
ULC
CAN/ULC-S524-2019
Standard for the Installation of Fire Alarm Systems
6.3.1.8.
9.9.4.12.(1)
ULC
CAN/ULC-S531-2019
Standard for Smoke Alarms
2.13.2.1.(3)
9.3.4.5.(3)
9.5.4.5.(3)
9.6.4.10.(3)
9.7.4.3.(4)
9.8.4.2.(3)
9.9.4.13.(2)
ULC
CAN/ULC-S536-2019
Standard for Inspection and Testing of Fire Alarm Systems
6.3.2.2.(1) to (3)
6.3.2.4.
ULC
CAN/ULC-S537-2019
Standard for Verification of Fire Alarm Systems
9.9.4.12.(2)
ULC
CAN/ULC-S540-13
Standard for Residential Fire and Life Safety Warning Systems: Installation, Inspection, Testing and Maintenance
2.13.2.1.(4)
ULC
CAN/ULC-S552-14
Standard for the Maintenance and Testing of Smoke-Alarms
6.3.2.6.(2)
ULC
CAN/ULC-S553-14
Standard for the Installation of Smoke-Alarms
9.3.4.5.(3)
9.5.4.5.(3)
9.6.4.10.(3)
9.7.4.3.(5)
9.8.4.2.(3)
9.9.4.13.(2)
ULC
CAN/ULC-S561-13
Standard for Installation and Services for Fire Signal Receiving Centres and Systems
6.3.1.2.(2)
9.7.4.1.(2)
9.7.4.2.(2)
ULC
CAN/ULC S601 14
Standard for Shop Fabricated Steel Aboveground Tanks for Flammable and Combustible Liquids
4.3.1.2.(1)
4.3.3.2.(1)
4.3.7.4.(2)
4.3.13.5.(1)
ULC
CAN/ULC S602 14
Standard for Steel Aboveground Tanks for Fuel Oil and Lubricating Oil
4.3.1.2.(1)
ULC
ULC S60